Text on the drawing
WOOD STRUCTURAL SHEAR PANEL WHERE OCCURS, SEE STRUCTURAL DRAWINGS 1 LAYER 5/8" TYPE 'X' GYP. BD. EACH SIDE 2X4 STUDS AT 24" O.C. MAX., SEE STRUCTURAL DRAWINGS 1" AIR GAP. PROVIDE RESILIENT DRAFT STOPS AT MAX. 10'-0" HORIZ. SPACING 3 1/2" BATT INSULATION 1 LAYER 5/8" TYPE 'X' GYP. BD. EACH SIDE 1 HOUR RATED PER UL DESIGN No. U341 AND STC 57 PER CALIFORNIA OFFICE OF NOISE CONTROL ASSEMBLY No. 1.2.4.1.5.4. PROVIDE FIRE BLOCKING AT CEILING AND FLOOR LEVELS N.T.S.