Electrical Service Mast Thru Roof - Section - typical mep detail drawing, DWG
Preview of electrical service mast thru roof - section. The DWG is fully editable.

Codes and approvals referenced

CEC 230.CEC 230.24

Text on the drawing

2" RIGID GALV. STEEL MAST, 18" MIN. ABOVE ROOF (CEC 230.24(A) EXC. 3) SERVICE DROP ATTACHMENT; GUY TO BLOCKING WHERE MAST > 30" ABOVE ROOF 2X BLOCKING W/ MAST STRAPS, PER UTILITY STANDARD MAST, CLEARANCES AND ATTACHMENT PER SERVING UTILITY (E.G. PG&E GREENBOOK) AND CEC 230. SERVICE DROP 3'-0" MIN. FROM WINDOWS / DOORS; MAST WITHIN 4'-0" OF ROOF EDGE. METER BELOW PER UTILITY. MAST FLASHING / ROOF JACK SEALED TO MAST AND ROOFING N.T.S.