TYPDETAIL

Home / MEP

Fire Damper at Rated Wall Detail - typical mep detail drawing, DWG
Preview of fire damper at rated wall detail. The DWG is fully editable.

Text on the drawing

UL 555 FIRE DAMPER W/ FUSIBLE LINK, RATING = WALL RATING STEEL SLEEVE & RETAINING ANGLES, 1" MIN. LAP EA. SIDE ACCESS DOOR W/ CAM FASTENERS RATED WALL SLEEVE-TO-OPENING CLEARANCE 1/8" PER FT. OF PERIMETER. INSTALL PER MFR. UL LISTING. ACCESS DOOR 12"X12" MIN. WITHIN REACH OF FUSIBLE LINK, LABELED "FIRE DAMPER". N.T.S.

More mep details

Transverse Section - DWG drawing

Transverse Section

Longitudinal Section - DWG drawing

Longitudinal Section

Anchor at Deck Detail - DWG drawing

Anchor at Deck Detail

Brace Connection at Deck Detail - DWG drawing

Brace Connection at Deck Detail

Rod to Strut Connection Detail - DWG drawing

Rod to Strut Connection Detail

Bath Exhaust Fan (roof) Detail - DWG drawing

Bath Exhaust Fan (roof) Detail

Bath Exhaust Fan (wall) Detail - DWG drawing

Bath Exhaust Fan (wall) Detail

Range Hood Detail (roof) - DWG drawing

Range Hood Detail (roof)