Codes and approvals referenced
Text on the drawing
12" MIN. GROUNDING ELECTRODE CONDUCTOR, SIZE PER CEC TABLE 250.66 LISTED DIRECT-BURIAL CLAMP OR EXOTHERMIC WELD 5/8" DIA. X 8'-0" COPPER-CLAD STEEL GROUND ROD DRIVE ROD FULL 8'-0" (CEC 250.53). WHERE 25 OHMS IS NOT MET, ADD 2ND ROD 6'-0" MIN. APART (10'-0" PREFERRED). N.T.S.