Text on the drawing

STEEL POLE W/ HANDHOLE & INTERNAL GROUND LUG (4) 1" A.B. W/ LEVELING NUTS, GROUT 1" UNDER BASE PL. (6) #6 VERT. W/ #3 TIES @ 12" 24" DIA. X 8'-0" DEEP CONC. PIER (2'-6" ABOVE GRADE AT PARKING) FOUNDATION SHOWN FOR POLES TO 25'-0" & EPA PER PLAN; VERIFY W/ POLE MFR. CHAMFER TOP 3/4". f'c = 3,000 PSI. PROVIDE VIBRATION DAMPER IN POLES 20'-0" AND TALLER. GROUND POLE PER CEC 250. 1" CONDUIT FROM PULL BOX DETAIL # - LIGHT POLE FOUNDATION NOT TO SCALE