Plumbing Vent Roof Penetration - Section - typical mep detail drawing, DWG
Preview of plumbing vent roof penetration - section. The DWG is fully editable.

Codes and approvals referenced

CPC 906.1CPC 906.2

Text on the drawing

VENT PIPE PER PLUMBING PLAN, 6" MIN. ABOVE ROOF (CPC 906.1) NEOPRENE / LEAD BOOT FLASHING, COLLAR SEALED TO PIPE FLANGE UNDER UPSLOPE SHINGLES, OVER DOWNSLOPE SHINGLES ROOF SHEATHING AND UNDERLAYMENT LOCATE VENT 10'-0" MIN. FROM OPENABLE WINDOWS / AIR INTAKES OR 3'-0" ABOVE (CPC 906.2). DO NOT CUT RAFTERS / TRUSSES FOR PENETRATION WITHOUT ENGINEER APPROVAL. N.T.S.