Codes and approvals referenced
Text on the drawing
MECHANICAL UNIT 600 LB. MAX. UNIT RAIL SPACING UNIT BASE RAIL W/ 1/2" DIA. X 5" LAG @ 24" O.C. INTO SLEEPER & BLOCKING (4 MIN.) P.T. 4X4 SLEEPER, FLASHED & COUNTER-FLASHED 15/32" WSP ROOF SHEATHING DOUBLE 2X10 JOIST UNDER EA. SLEEPER, 16d @ 12" O.C. 4X4 BLOCKING @ 24" O.C. IN SIMPSON HU44 HANGERS 2X10 ROOF JOISTS @ 16" O.C. FOR UNITS TO 600 LB. CENTERED OVER JOISTS SPANNING 14'-0" MAX. HEAVIER UNITS: SUPPORT BEAMS PER PLAN. ANCHORAGE FOR SEISMIC PER ASCE 7 CH. 13 (Fp = 0.6 Wp MIN. SHOWN). FRAME DUCT OPENINGS PER S-FLR-077. N.T.S.