Split-Type Air Conditioning Unit Detail - typical mep detail drawing, DWG
Preview of split-type air conditioning unit detail. The DWG is fully editable.

Text on the drawing

INSULATION PLATE INDOOR UNIT ON MFR. MOUNTING PLATE AUTO LOUVER (VERTICAL) MANUAL LOUVER (HORIZONTAL) VINYL TAPE. APPLY AFTER DRAINAGE TEST CONNECTING CABLE, DRAIN HOSE, LIQUID & GAS SIDE PIPING IN LINE-SET COVER OUTDOOR UNIT 36"x18"x3" MIN. PRECAST PAD INDOOR UNIT: MFR MOUNTING PLATE SCREWED TO MIN. (2) WALL STUDS WITH (6) #10 x 2-1/2" WOOD SCREWS MIN., LEVEL. OUTDOOR UNIT: ON 36"x18"x3" MIN. PRECAST PAD ON COMPACTED GRADE, ANCHORED WITH MFR KIT OR (4) 1/4" CONCRETE SCREWS; MFR CLEARANCES. DRAINAGE TEST: REMOVE FILTERS AND POUR WATER INTO HEAT EXCHANGER. N.T.S.