TYPDETAIL

Home / MEP

Telecom Room Layout - Plan - typical mep detail drawing, DWG
Preview of telecom room layout - plan. The DWG is fully editable.

Text on the drawing

9'-0" MIN. 12'-0" MIN. 3/4" FIRE-RATED PLYWOOD BACKBOARD, 8'-0" HIGH, PAINTED (2 WALLS MIN.) TMGB & DEDICATED 20A CIRCUITS SIZE PER TIA-569. NO PLUMBING / DRAINS ABOVE ROOM. 24/7 HVAC, 64-75 DEG. F. LIGHTING 50 FC AT 3'-0" A.F.F. DOOR 3'-0" X 7'-0" MIN., OUTSWING, LOCKABLE. BOND RACKS, CABLE TRAY AND BACKBOARD TO TMGB. 19" RACK, 36" CLR. FRONT & REAR N.T.S.