Codes and approvals referenced
Text on the drawing
GAS METER (1 PER UNIT) MAIN - SIZE PER TABLE WATER HEATER BRANCH WATER HEATER BTU/H & CONN. PER MFR. RANGE BRANCH RANGE BTU/H PER NAMEPLATE OTHER GAS APPLIANCE WHERE OCCURS = APPLIANCE SHUTOFF VALVE + SEDIMENT TRAP (CPC 1212.5, 1212.7) GAS NOTES 1. EXISTING GAS PIPING MAY REMAIN ONLY WHERE ITS SIZE IS NOT LESS THAN THE TABLE. REPLACE ANY SMALLER SEGMENT WITH SCHEDULE 40 BLACK STEEL. LABEL EACH SEGMENT "EXIST." OR "NEW". 2. WATER HEATER: SHUTOFF AND SEDIMENT TRAP AT HEATER. VENT PER MFR., TERMINATION CLEARANCES PER MFR. 3. PRESSURE TEST NEW AND ALTERED GAS PIPING PER CPC 1213.0 BEFORE METER TURN-ON. SUPPORT AND PROTECT PIPING PER CPC 1210.0. 4. PIPE SIZING PER CPC 1215 / TABLE 1215.2(1), LONGEST-LENGTH METHOD. GAS ROUTES ARE DIAGRAMMATIC. EACH UNIT (DIAGRAMMATIC) N.T.S.