Text on the drawing
PIPE W/ INSULATION INSULATION SHIELD (MSS SP-58 TYPE 40) W/ HIGH DENSITY INSERT 1/4" STEEL BRACKET, GALV., SIZED TO SUIT INSULATION (2) 1/2" DIA. S.S. WEDGE ANCHORS, 2 1/2" MIN. EMBED (ICC-ES ESR) CONC. WALL SUPPORT SPACING PER MSS SP-58 TABLE FOR PIPE SIZE. BRACKET AND ANCHORS SIZED FOR PIPE WEIGHT FULL OF WATER PLUS INSULATION. SEISMIC BRACING PER MEP / PLAN WHERE REQUIRED. N.T.S.