Codes and approvals referenced
Text on the drawing
1'-6 3/4" MIN. WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT DUE TO EARTHQUAKE MOTION. STRAPPING SHALL BE AT POINTS WITHIN THE UPPER ONE-THIRD (1/3) AND LOWER ONE THIRD (1/3) OF ITS VERTICAL DIMENSIONS. AT THE LOWER POINT, A MINIMUM DISTANCE OF FOUR INCHES SHALL BE MAINTAINED ABOVE THE CONTROLS WITH THE STRAPPING PER CPC 507.2. PROVIDE SOLID BLOCKING AT WALL FOR STRAPPING ATTACHMENT. CONTROLS WATER HEATER PLATFORM MAY OCCUR. SEE FLOOR PLAN VERIFY THE SIZE OF WATER HEATER WITH THE NUMBER OF STRAPS USED PER GENERAL NOTES DIVISION 15. N.T.S.