Text on the drawing
CMU WALL CAST-IN-PLACE WALL CMU CONTROL JOINT @ 25'-0" O.C. MAX., SEALANT O/ BACKER ROD CONTRACTION JOINT @ 20'-0" O.C. MAX., 1/4 WALL THICKNESS EXPANSION JOINT @ 90'-0" O.C. MAX. AND AT CORNERS, 1/2" FILLER STEP FOOTINGS AND WALLS ONLY AT JOINTS. HORIZONTAL REINF. CONTINUOUS THRU CONTROL / CONTRACTION JOINTS; INTERRUPTED AT EXPANSION JOINTS W/ SMOOTH DOWELS. WATERSTOP AT RETAINED FACE WHERE REQUIRED. 1/4" = 1'-0"