TYPDETAIL

Home / Civil

Thrust Block - 10" Pipe Bend Detail - typical civil detail drawing, DWG
Preview of thrust block - 10" pipe bend detail. The DWG is fully editable.

Text on the drawing

PLAN SECTION 10" PRESSURE PIPE PER PLAN 90-DEG BEND, JOINTS PER PLAN 2500 PSI CONC. BLOCK, 4.5 SF MIN. BEARING (36" X 18" FACE) UNDISTURBED TRENCH WALL, POUR AGAINST KEEP CONC. OFF JOINTS, WRAP FITTING IN 8 MIL POLYETHYLENE 1. BEARING AREA BASED ON 150 PSI TEST PRESSURE, 90-DEG BEND, 2000 PSF ALLOWABLE SOIL BEARING. 2. ARROW = THRUST DIRECTION; CENTER BLOCK FACE ON IT. ADJUST PER AGENCY STANDARD / SOILS REPORT. DETAIL # - THRUST BLOCK - 10" PIPE BEND NOT TO SCALE