Text on the drawing
BRICK VENEER, 1" AIR SPACE, TIES @ 16" O.C. EA. WAY THRU-WALL FLASHING & WEEPS OVER RELIEF ANGLE 3/8" SOFT JOINT: BACKER ROD & SEALANT UNDER ANGLE 600S162-54 STUDS @ 16" O.C., BYPASS FRAMED PAST SLAB EDGE VERTICAL SLIDE CLIP EA. STUD: (3) #12 SCREWS IN SLOTS, 1/4" EXP. ANCHOR TO SLAB MINERAL WOOL FIRESAFING IN 1" GAP, FULL SLAB DEPTH L5X5X3/8 GALV. RELIEF ANGLE, 1/2" DIA. BOLT TO EA. STUD W/ BACKING PLATE RELIEF ANGLE AT EA. FLOOR ABOVE 30'-0" (TMS 402). STUDS AND CLIPS CARRY VENEER WEIGHT + WIND AT L/600. SLIDE CLIP ALLOWS 3/4" SLAB DEFLECTION; DO NOT TIGHTEN SCREWS IN SLOTS. FIRESTOP PER LISTED SYSTEM. N.T.S.